Thermostatic Mixing Valve Kit for Safety showers

The ComfortLine series of thermostatic mixing valves are special mixing valves designed for Eye showers and Safety showers, ensuring highly precise water temperature control and protection against scalding. A continuous supply of hot and cold water is required for this purpose. The thermostatic mixing valves ensure that the correct water temperature is always available at the point of use and prevent unwanted temperature fluctuations.

Article-No.: BR710960

Or call us directly at: +49 40 538 092 70
(Mo – Thu from 8 a.m. to 5 p.m. and Fri from 8 a.m. to 14 p.m.)

Downloads

Assembly and Operating Instructions

Technical specifications

MaterialBrass
Colourbrass, black
Height (mm)300
Width (mm)290
Length/Depth (mm)235
Weight (kg)5,12
Adjustment rangeTemperature range: 20–43°C, preset to 22°C
Compression stagePN 10
Operating pressure (bar)max. 10,0
Differential Pressure Mixingmax. 3 bar
Differential pressure between cold and hot water supplymax 0.3 bar
Differential pressure for activating the bypass functionat least 0.5 bar
Media temperaturemin. 0°C / max. 95°C
Volume flow (l/min)160 liters per minute at a differential pressure of 1.0 bar
Air flow rate in bypass mode90 liters per minute at a differential pressure of 1.0 bar
Water connections1 1/4″ female
Water outlet / drain1 1/4″ female

More about this product

Product description

The ComfortLine series of thermostatic mixing valves are special mixing valves designed for Eye showers and Safety showers, ensuring highly precise control of water temperature and protection against scalding. A continuous supply of hot and cold water is required for this purpose. The thermostatic mixing valves ensure that the correct water temperature is always available at the point of use and prevent unwanted temperature fluctuations.

The scald protection reliably protects the user from scalding. The scald protection is activated if the hot water temperature rises uncontrollably or if the cold water supply fails.

The thermostatic mixing valve ensures a continuous water supply even if the hot water supply fails (e.g., when the hot water is turned off). This function is activated when the pressure differential between the cold and hot water exceeds 0.5 bar. In this case, cold water flows out at the draw-off point (bypass function).

Technical Description

  • Adjustment range: 20–43°C, preset to 22°C
  • Automatic inspection of the cold- and hot-water supply lines
  • Concealed water temperature control with scald protection set at 43°C
  • Hot water shuts off automatically if the cold water supply fails
  • Flow rate: 160 liters per minute at a differential pressure of 1.0 bar; flow rate in bypass mode: 90 liters per minute at a differential pressure of 1.0 bar
  • Hot water connection: 1 1/4″ female; cold water connection: 1 1/4″ female; water outlet: 1 1/4″ female
  • Integrated check valves in the cold- and hot-water connections to protect the drinking water
  • Dimensions (H x W x D): 300 x 290 x 235 mm
  • in accordance with BGI/GUV-I 850-0, DIN 1988, and EN 1717
  • according to ANSI Z358.1-2014 and EN 15154-2:2006